MSI-TR1B-01
Safety relay
Series | MSI-TB |
Application | Evaluation unit for type 2 single beam safety devices in accordance with IEC/EN 61496 |
Functions | "Error" signal output "Safety ON" signal output Contactor monitoring (EDM) Periodic function test Start/restart interlock (RES) |
Restart | Automatic Manual |
Type | 2, IEC/EN 61496 |
SIL | 1, IEC 61508 |
SILCL | 1, IEC/EN 62061 |
Performance Level (PL) | c, EN ISO 13849-1 |
MTTFd | 78 years, EN ISO 13849-1 |
PFHD | 8.8E-08 per hour |
Mission time | 20 years, EN ISO 13849-1 |
Category | 2, EN ISO 13849-1 |
Protective circuit | Polarity reversal protection Short circuit protected |
Continuous current per current path, max. | 2 A |
Supply voltage UB | 24 V, DC, -20 ... 20 % |
Current consumption, max. | 200 mA, Without external load |
Power consumption, max. | 4.8 W, For 24 V, plus output load |
Residual ripple | -15 ... 15 % |
Fuse | External with max. 3.15 A semi time-lag |
Number of digital switching inputs | 4 Piece(s) |
Type | Digital switching input |
Switching voltage high, min. | 18.2 V |
Switching voltage low, max. | 2.5 V |
Switching voltage, type. | 23 V |
Voltage type | DC |
Function | Control input for contactor monitoring (EDM) |
Function | Control input for receiver |
Function | RES/Start control input |
Function | Control input for Reset |
Function | Restart interlock control input |
Number of safety-related switching outputs (OSSDs) | 2 Piece(s) |
Number of digital switching outputs | 3 Piece(s) |
Type | Safety-related switching output OSSD |
Voltage type | DC |
Current load, max. | 2,000 mA |
Switching element | Relay, NO |
Switching element | Relay, NO |
Type | Digital switching output |
Switching voltage high, min. | 18.2 V |
Switching voltage low, max. | 2.5 V |
Switching voltage, type. | 23 V |
Voltage type | DC |
Switching element | Transistor, PNP |
Function | "Safety ON" signal output |
Switching element | Transistor, PNP |
Function | "Error" signal output |
Switching element | Transistor, PNP |
Function | Test signal output (transmitter) |
Number of outputs, safety-oriented, non-delayed, contact-based | 2 Piece(s) |
Number of outputs, safety-oriented, delayed, contact-based | 0 Piece(s) |
Number of outputs, signaling function, non-delayed, contact-based | 0 Piece(s) |
Response time | 20 ms |
Switch-on delay | 2 s |
Regression delay | 20 ms |
Sensor response time on test request | 0.5 ... 60 ms |
Number of connections | 1 Piece(s) |
Function | Connection to device Voltage supply |
Type of connection | Terminal |
Type of terminal | Screw terminal |
No. of pins | 16 -pin |
Connection cross sections | 0.2 to 2.5 mm² |
Dimension (W x H x L) | 22.5 mm x 99 mm x 114.1 mm |
Housing material | Plastic |
Plastic housing | Unreinforced polyamide PA |
Net weight | 200 g |
Housing color | Gray |
Type of fastening | Snap-on mounting |
Type of display | LED |
Number of LEDs | 4 Piece(s) |
Ambient temperature, operation | -30 ... 60 °C |
Ambient temperature, storage | -40 ... 70 °C |
Relative humidity (non-condensing) | 0 ... 95 % |
Degree of protection | IP 40 |
Protection class | II |
Approvals | TÜV Süd c TÜV Rheinland US |
US patents | US 6,418,546 B |
Customs tariff number | 85371098 |
ECLASS 5.1.4 | 27371800 |
ECLASS 8.0 | 27371819 |
ECLASS 9.0 | 27371819 |
ECLASS 10.0 | 27371819 |
ECLASS 11.0 | 27371819 |
ECLASS 12.0 | 27371819 |
ECLASS 13.0 | 27371819 |
ECLASS 14.0 | 27371819 |
ECLASS 15.0 | 27371819 |
ETIM 5.0 | EC001449 |
ETIM 6.0 | EC001449 |
ETIM 7.0 | EC001449 |
ETIM 8.0 | EC001449 |
ETIM 9.0 | EC001449 |
ETIM 10.0 | EC001449 |